Everwell CF-25AV

Дастури истифодабарии хати моеъи хунуккунандаи филтри хушккунандаи Everwell

Model: CF-25AV | Brand: Everwell

Маҳсулот ба охир расидview

The Everwell CF-25AV Filter Drier is designed for use in refrigerant liquid lines. It effectively removes moisture and contaminants from the refrigerant, protecting the compressor and other system components from damage and ensuring optimal system performance. This product is suitable for various refrigeration and air conditioning systems, including chest freezers, commercial kegerators, compact fridges, compressor wine fridges, miniature kegerators, mini freezers, mini fridges, portable fridges, undercounter freezers, and upright freezers.

Ten Everwell CF-25AV filter driers with charging valves, arranged in a row.

Image: A set of ten Everwell CF-25AV filter driers, showcasing their copper construction and charging valves.

Маълумот оид ба бехатарӣ

Огоҳӣ: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm (Proposition 65). Always handle with care and follow all local regulations regarding refrigerant handling and disposal.

  • Always wear appropriate personal protective equipment (PPE), including safety glasses and gloves, when working with refrigerants and refrigeration systems.
  • Ensure the system is depressurized before attempting any installation or maintenance.
  • Avoid direct contact with refrigerant, as it can cause frostbite.
  • Work in a well-ventilated area to prevent the accumulation of refrigerant vapors.
  • Do not apply excessive force or bend the copper tubing excessively, as this can lead to damage or leaks.

Насб ва насб

The Everwell CF-25AV filter drier is designed for easy integration into existing or new refrigeration systems. It features a 1/4" inlet and 1/4" outlet, along with a charging valve for convenience.

  1. Омодасозии система: Ensure the refrigeration system is completely evacuated and free of pressure before beginning installation.
  2. Самти ҷараёнро муайян кунед: The filter drier should be installed in the liquid line between the condenser and the metering device (e.g., expansion valve). While filter driers are typically bi-directional, it is good practice to ensure the flow aligns with any internal markings if present.
  3. Cutting Tubing: Carefully cut the existing liquid line tubing to the appropriate length to accommodate the filter drier. Ensure clean, burr-free cuts.
  4. Brazing/Soldering: Braze or solder the filter drier into the liquid line using appropriate techniques and materials. Protect the drier body from excessive heat during brazing to prevent damage to the desiccant material inside. Use a wet rag or heat sink paste around the drier body.
  5. Санҷиши ихроҷ: After installation, perform a thorough leak check using nitrogen or a suitable leak detection method to ensure all connections are secure and leak-free.
  6. Эвакуатсия ва пуркунӣ: Evacuate the system to a deep vacuum to remove all non-condensable gases and moisture. Then, charge the system with the appropriate refrigerant according to the manufacturer's specifications. The integrated charging valve can be used for this purpose.
Аз наздики view of multiple Everwell CF-25AV filter driers, showing the copper tubing and charging valves.

Тасвир: Муфассал view of several filter driers, highlighting their construction and connection points.

A single Everwell CF-25AV filter drier with its charging valve, isolated against a white background.

Image: A single filter drier unit, clearly showing the main body, copper tubes, and the brass charging valve.

Принсипҳои фаъолият

The filter drier serves as a critical component in a refrigeration system's liquid line. Its primary functions are:

  • Тоза кардани намӣ: The desiccant material inside the drier absorbs moisture that may be present in the refrigerant, preventing the formation of ice in the metering device and avoiding acid formation which can corrode system components.
  • Contaminant Filtration: A filter screen or pad within the drier traps solid contaminants such as dirt, metal shavings, and sludge, preventing them from circulating through the system and damaging the compressor or clogging the metering device.

By performing these functions, the filter drier helps maintain the longevity and efficiency of the refrigeration system.

Нигоҳдорӣ

Filter driers are generally considered maintenance-free components, but they have a finite capacity for moisture and contaminant absorption. They should be replaced under the following circumstances:

  • After Compressor Burnout: A compressor burnout can introduce significant contaminants and acid into the system, necessitating the replacement of the filter drier.
  • After System Opening: Any time the refrigeration system is opened for service (e.g., component replacement), the filter drier should be replaced to ensure any introduced moisture or contaminants are removed.
  • Signs of Restriction: If there are signs of restricted refrigerant flow in the liquid line (e.g., a significant temperature drop across the drier, reduced system performance), the filter drier may be clogged and require replacement.

Regular system checks by a qualified technician can help identify when a filter drier replacement is necessary.

Мушкилкушо

While filter driers are passive components, issues related to them can manifest as system problems. Here are some common troubleshooting scenarios:

  • Restricted Refrigerant Flow: If the filter drier becomes saturated with moisture or clogged with debris, it can restrict refrigerant flow. Symptoms include high head pressure, low suction pressure, and a significant temperature difference across the drier (the outlet being noticeably colder than the inlet).
  • Moisture-Related Issues: Inadequate moisture removal can lead to ice formation at the metering device, causing intermittent or complete blockage of refrigerant flow. This might present as fluctuating system performance or complete shutdown.
  • Acid Formation: If moisture and contaminants are not removed, they can react with the refrigerant and oil to form acids, leading to corrosion of internal components. This is often a long-term issue but can be indicated by oil analysis.

If any of these issues are suspected, it is recommended to consult a qualified HVAC/R technician for diagnosis and repair, which will likely involve replacing the filter drier and potentially other system components.

Мушаххасоти

ХусусиятТафсилот
Рақами моделCF-25AV
Андозаи вуруд1/4 инч
Андозаи баромад1/4 инч
Molecular Sieve (Desiccant)25 грамм
Quantity per Bag10 адад
Item Weight (per unit)Approximately 0.22 lbs (2.2 lbs for 10 units)
Андозаҳои бастаҳо12.13 x 8.62 x 1.81 inches (for 10 units)
ИстеҳсолкунандаЭвервелл
Diagram showing the approximate dimensions of the filter drier, indicating a length of 9 inches and a main body length of 4 inches.

Image: A diagram illustrating the approximate dimensions of the filter drier, including overall length and body length.

Кафолат ва дастгирӣ

This product is typically covered by a standard return policy. For specific warranty details, terms, and conditions, please refer to the purchase agreement or contact the seller directly. Everwell products are designed for professional use; therefore, it is recommended that installation and service be performed by qualified technicians.

For technical support or inquiries regarding product performance, please reach out to Everwell customer service through their official channels or the retailer from whom the product was purchased.

Ҳуҷҷатҳои марбут - CF-25AV

Пешview Everwell High Efficiency Air-Handler Installation and Owner's Manual
Comprehensive installation and owner's manual for Everwell High Efficiency Air-Handler indoor split-system units (1.5 to 5 tons, up to 15 SEER), covering safety, general information, applications, electrical wiring, refrigerant connections, condensate drain tubing, air filter installation, wiring diagrams, and electric wiring gauge specifications.
Пешview Дастури насб ва истифодаи насоси гармидиҳӣ ва агрегати хунуккунии Everwell
Comprehensive installation and operation manual for Everwell 1.5-5 Ton Heat Pump & Cooling Units with R454B refrigerant, featuring up to 14.3 SEER2 efficiency. Includes safety precautions, unit setup, refrigerant handling, electrical connections, and troubleshooting.
Пешview Everwell CAC3614HA15 таркид View ва Рӯйхати қисмҳо
Муфассал таркид view ва рӯйхати қисмҳои ҳамаҷонибаи воҳиди HVAC Everwell CAC3614HA15, аз ҷумла мушаххасоти ҷузъҳо ва рақамҳои қисм барои хидмат ва нигоҳдорӣ.
Пешview Дастури корбар Everwell MGTC-20 Series Function Wi-Fi
Дастури корбар барои кондитсионерҳои Everwell MGTC-20 Series, ки тафсилоти танзими функсияи Wi-Fi, назорати барнома, идоракунии дастгоҳ ва ҳалли мушкилотро дар бар мегирад.
Пешview Дастури дастури кондитсионери навъи Everwell Split
Роҳнамои ҳамаҷониба барои кондитсионерҳои навъи Everwell, ки тафсилоти насб, истифода, чораҳои бехатарӣ, нигоҳдорӣ ва қадамҳои бартараф кардани мушкилотро дар бар мегирад.
Пешview Дастурҳои насби насоси гармидиҳӣ ва кондитсионери Everwell Split System (15 SEER, R410A)
Дастури мукаммали насб барои агрегатҳои насоси гармидиҳӣ ва кондитсионери Everwell 15 SEER Split System (1.5-5 тонна, R410A). Андозаҳо, фазои хизматрасонӣ, қубурҳо, ноқилҳо, хусусиятҳои барқӣ, маҳдудиятҳои кор, тартиби насб, интихоби макон, коркарди яхдон, хушккунии вакуумӣ, изолятсия, озмоиш ва ҳалли мушкилотро дар бар мегирад.